75 Watts Power Supply in Metal housing. Free air convection, Galvanic insulated, Continuous short circuit protected, Overload and low voltage protected, Soft start and auto-recovery, High reliability, shock and vibration resistant.
HSW00751.05T (5V / 7.5A) |
HSW00751.09T (9V / 7.6A) |
HSW00751.12T (12V / 6.0A) |
HSW00751.15T (15V / 5.0A) |
HSW00751.24T (24V / 3.2A) |
|
Model |
HSW00751 |
Power |
75W |
Nominal AC Input |
100... 240Vac |
Input Range AC |
90... 265Vac |
Input Range DC |
110... 375Vdc |
Input Frequency |
47... 63Hz |
Hold-Up Time |
40ms |
Inrush Current Protection |
NTC <32A |
Autostart |
Soft start 50ms |
Output Voltage |
5V |
9V |
12V |
15V |
24V |
Adjust Range Vout |
4,9... 5,5V |
8,6... 9,9V |
11,4... 13,2V |
14,3... 16,5V |
22,5... 28,5V |
Ripple & Noise mVpp |
15mV |
15mV |
20mV |
20mV |
50mV |
Nominal Output Current |
7,5A |
7,6A |
6A |
5A |
3,2A |
Power Boost <=60°C/60s |
9A |
9,1A |
7,2A |
6A |
3,8A |
Stability at Load Switch |
±0,1% |
±0,5% |
±0,3% |
±0,2% |
±0,1% |
Transient Time |
< 1ms |
Efficiency |
90% |
Basic load |
Idling-proof |
Short Circuit Protection |
Continuous |
Ambient Operation Temperature |
-20°C... +70°C |
Cooling |
Natural convection |
Temperature Monitoring |
Upon request |
Dimensions (WxHxD) |
50x102x96mm |
IP-Range |
IP20 |
Safety Norms |
CSA UL CE according to IEC60950-1 |
Safety IEC |
EN60950-1 EN50178 EN60204-1 |
Safety Class 1(A) |
VDE0100 VDE0805 |
Input to Output Isolation |
3000Vac |
Climatic Class, Humidity |
3k3, 90% non condensing |
EMI |
EN55022B EN61000-3-2A |
EMS |
EN61000-6-2,3 |
MTBF IEC61709 |
500000h |
Power Good Relay |
Galvanic insulated 60Vdc |
Sense operation |
Yes 5V-model ±200mV |
Remote Shutdown |
No |
Ordering options |
Protective Coating |
Options |
see Datasheet |
|