The device FD39 serves to measure the flow of nonaggressive fluid and gaseous media. It is imperative to consult the manufacturer before using the device for aggressive media because media-compatible materials need to be used for the measuring path. Typical applications are display unit, volume measuring unit, flow security. The measuring path comprises a measuring panel with differential pressure removal boreholes and two independent pressure sensors. The differential pressure created at the measuring panel is measured by the pressure sensors and turned into a root extracted analogue output signal by the microprocessor-controlled electronics. The standard signals 0/4…20 mA and 0…10V are available for the analogue output.